Rated Voltage |
Three phase 1 – 12 KV single phase 1- 24 KV |
|
Power output |
25 – 500 kvar for three phase units 25 – 600 kvar for single phase units |
|
Frequency |
50/60 Hz |
|
Reference standards |
IEC 60871-1:1997 EN 60871-1:1997 IEC 60871-4:1997 EN 60871-4:1997 |
|
Over voltage Max |
Un +10% (12 hours in 24 hours daily) Un +15% (30 minutes) Un +20% (5 minutes) Un +30% (1 minutes) |
|
Over current |
1,3 * ln |
|
Limit of inrush current |
max. 100xln |
|
Basic insulation level |
20/60 kv; 28/75 kv; 38/95 kv; |
|
Life expectation |
>100 000 hours |
|
Nivel IP protection |
IP 00, indoor and outdoor |
|
Temperature Category |
“C” -40° / maximum of 50° |
|
Type of cooling |
Air Natural |
|
Humidity |
maximum 95% |
|
Altitude of site |
1000 m above mean sea level |
|
Mounting |
Horizontal/Vertical |
|
Mounting arrangement |
Mounting brackets |
|
Device for internal protection |
internal element fuse |
|
Telorance |
-5 / +10% |
|
Test Voltage |
4,3 * Un DC |
|
Dielectric loss |
0,07 W/kvar |
|
Capacitor losses |
0,15 W/kvar |